REMOTE CONDENSER RECOVERY/EVACUATION
1. Press the power button to stop the ice machine.
2. Install manifold gauges, scale and recovery unit or
two-stage vacuum pump.
3. Open high and low side on the manifold gauge
set.
4. Perform recovery or evacuation:
A. Recovery: Operate the recovery unit as
directed by the manufacturer’s instructions.
B. Evacuation prior to recharging: Pull the
system down to 500 microns. Then, allow the
pump to run for an additional hour. Turn off
the pump and perform a standing vacuum
leak check.
NOTE: Check for leaks with an electronic leak
detector after charging the ice machine.
5. Follow the Charging Procedures.