Manitowoc I0320 Especificaciones Pagina 208

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 272
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 207
208 Part Number STH025 2/14
CONNECTIONS
Make these connections:
Suction side of the compressor through the suction
service valve.
Discharge side of the compressor through the
discharge service valve.
Receiver outlet service valve, which evacuates the
area between the check valve in the liquid line and
the liquid line solenoid.
Access (Schraeder) valve on the discharge line
quick-connect fitting, located on the outside of the
compressor/evaporator compartment. This
connection evacuates the condenser. Without it,
the magnetic check valves would close when the
pressure drops during evacuation, preventing
complete evacuation of the condenser.
NOTE: Manitowoc recommends using an access
valve core removal and installation tool on the
discharge line quick-connect fitting. This permits
access valve core removal. This allows for faster
evacuation and charging, without removing the
manifold gauge hose.
Important
Recovery/evacuation of a remote system
requires connections at four points for complete
system evacuation.
Vista de pagina 207
1 2 ... 203 204 205 206 207 208 209 210 211 212 213 ... 271 272

Comentarios a estos manuales

Sin comentarios