Part Number 80-1230-9 6/08 215
REFRIGERANT RECOVERY/EVACUATION
Normal Self-Contained Model Procedures
Do not purge refrigerant to the atmosphere. Capture
refrigerant using recovery equipment. Follow the
manufacturer’s recommendations.
CONNECTIONS
Manifold gauge sets must utilize low loss fittings to
comply with U.S. Government rules and regulations.
Make these connections:
Suction side of the compressor through the suction
service valve.
Discharge side of the compressor through the
discharge service valve.
Important
Manitowoc Ice, Inc. assumes no responsibility for
the use of contaminated refrigerant. Damage
resulting from the use of contaminated refrigerant is
the sole responsibility of the servicing company.
Important
Replace the liquid line drier before evacuating and
recharging. Use only a Manitowoc (OEM) liquid line
filter-drier to prevent voiding the warranty.