Part Number 80-1230-9 6/08 177
4. Disconnect water level probe from control board.
Install jumper from control board “water level”
terminal to ground.
5. Move the toggle switch from ICE to OFF to ICE
position. Wait 45 seconds, then monitor the Water
Level Probe light.
Step 5 Jumper “water level” terminal to ground
Water Level
light is:
Compressor Cause
On Energizes
Replace water level
probe wiring.
(Verify defective
component – ohm wire
from connector
to connector.)
Off
Remains
de-energized
Replace
control board.
WATER LEVEL
PROBE LIGHT
DISCONNECT
WATER LEVEL PROBE.
JUMPER FROM
CONTROL BOARD
“WATER LEVEL” TO
GROUND