Part Number 80-1230-9 6/08 203
High Pressure Cutout (HPCO) Control
FUNCTION
Stops the ice machine if subjected to excessive high-
side pressure.
The HPCO control is normally closed, and opens on a
rise in discharge pressure.
CHECK PROCEDURE
1. Set ICE/OFF/CLEAN switch to OFF, (Manual
reset HPCO reset if tripped).
2. Disconnect main power supply to the ice
machine.
3. Connect manifold gauges to the access valves.
4. Hook voltmeter in parallel across the HPCO,
leaving wires attached.
5. Reconnect main power supply to the ice machine.
Specifications
Cut-Out Cut-In
450 psig ±10
(3103 kPa ±69)
31 bar ±.69
Automatic Reset
(Must be below 300 psig
(2068 kPa 20.68 bar) to reset.)