Water Level Probe Closed or Shorted
1. Disconnect the water level probe from the control
board.
2. Move the toggle switch to the ICE position, wait
45 seconds and then monitor the Water Level
Probe light.
Step 2 Disconnect water level probe from control board
“water level” terminal
Water Level
light is:
Compressor Cause
Off Remains
de-energized
Clean water
level probe.
On Energizes Replace control board.
DISCONNECT
WATER LEVEL PROBE.
WATER LEVEL
PROBE LIGHT