Part Number 80-01111-9 7/10 147
FREEZE CYCLE IS LONG, LOW ICE PRODUCTION
Water temperature is too high
Connect to a cold water supply, verify check valves
in faucets and other equipment are functioning
correctly
Dirty Condenser
Clean condenser
High air temperature entering condenser
Air temperature must not exceed 120°F (39°C)
Water inlet valve filter screen is dirty
Remove the water inlet valve and clean the filter
screen
Water inlet valve stuck open or leaking
Turn off ice machine, if water continues to enter ice
machine, verify water pressure is ok then replace
water inlet valve
Water inlet valve is not working
Water inlet valve must be replaced
Refrigeration problem
Refer to refrigeration diagnostics
Water escaping from sump during freeze cycle
Check standpipe and drain
Check for water tracking out of water circuit