C. SUCTION LINE OIL TRAPS
0 to 20 ft. (0 to 6.1 m) Rise: The ice machine head
section has one oil trap built in which allows for a
maximum condenser rise of 20 ft. (6.1 m) without
additional traps in the suction line.
21 to 35 ft. (6.4 to 10.7 m) Rise: The suction line
requires an additional oil trap (“S” type) to be installed.
Install the trap as close as possible to midpoint
between the ice machine head section and CVD
®
Condensing Unit. S-Trap Kits are available from
Manitowoc (refer to chart).
Do not form unwanted traps in refrigeration lines.
Never coil excess refrigeration tubing.
SV1751
21 FT. OR
MORE RISE
ADDITIONAL
TRAP KIT
REQUIRED.