Manitowoc CVD1375 Especificaciones Pagina 172

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 204
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 171
–170–
Water Regulating Valve
Function
The water regulating valve maintains the freeze cycle
discharge pressure. The valve setting for the
CVD1476 condensing unit is 240 psig.
Check Procedure
1. Determine if the head pressure is high or low (refer
to “Operational Pressure Chart”.
2. Verify the condenser water meets specifications.
3. Adjust valve to increase or decrease discharge
pressure (if discharge pressure remains high refer
to “Headmaster Control Valve Diagnostics” before
replacing valve).
4. Determine the temperature of the liquid line
entering the receiver by feeling it. This line is
normally warm; “body temperature.”
5. Using the information gathered, refer to the list for
diagnosis.
Problem (Freeze Cycle)
Valve not maintaining discharge pressure.
Valve incorrectly set, dirty or defective. Adjust valve
to 240 psig, clean or replace valve.
Discharge pressure extremely high; Liquid line
entering receiver feels hot.
Water regulating valve incorrectly set or not
opening. Verify Head Pressure Control Valve
operation before changing water regulating valve.
Discharge pressure low, Liquid line entering
receiver feels warm to hot.
Ice machine low on charge. Refer to “Refrigerant
Charge Verification.”
Vista de pagina 171
1 2 ... 167 168 169 170 171 172 173 174 175 176 177 ... 203 204

Comentarios a estos manuales

Sin comentarios