Manitowoc SR1801W Especificaciones Pagina 149

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 300
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 148
Part Number 80-1479-3 7/10 149
PROBLEM: ICE MACHINE CYCLES INTO HARVEST
BEFORE WATER CONTACT WITH THE ICE
THICKNESS PROBE
Step 1 Bypass the freeze time lock-in feature by
moving the ICE/OFF/CLEAN switch to OFF and back
to ICE.
Step 2 Disconnect the ice thickness probe from the
control board.
Step 3 Wait until water starts to flow over the
evaporator, then monitor the ice probe light:
Ice Probe Light Off
The ice probe light stays off, and the ice machine
remains in the Freeze sequence.
The ice thickness probe is causing the malfunction.
Verify that the ice thickness probe is adjusted correctly
and clean.
Ice Probe Light On
The ice probe light comes on, and 10 seconds
later, the ice machine cycles from Freeze to
Harvest.
The control board is causing the malfunction.
Vista de pagina 148
1 2 ... 144 145 146 147 148 149 150 151 152 153 154 ... 299 300

Comentarios a estos manuales

Sin comentarios