158 Part Number STH038 5/12
SYMPTOM
Alert icon on the display is flashing and the alert
indicates a T1, T2, T3, or T4 Fault.
CHECK PROCEDURE
Press the Menu button.
Scroll down to Service and press right arrow.
Scroll down to Diagnostics and press right arrow
Scroll down to Temp Sensors and press right
arrow to display thermistor temperature readings.
NOTE: An open thermistor will display -30
°C and a
shorted thermistor displays 246
°C.
Thermistor Test
1. Disconnect thermistor from control board and
measure resistance.
2. Measure temperature at the thermistor.
3. Compare measured resistance/temperature
readings to resistance/temperature relationship
chart.
A. Within 10% of the published resistance value
- Thermistor is good
B. Not within 10% of the published resistance
value - Thermistor is defective.
Control Board Test
1. Disconnect thermistor from control board - The
display temperature reading, dropping to
-30
°C)indicates the control board is good.
2. Short thermistor pins - The display temperature
reading, climbing to 246
°C indicates the control
board is good.