Manitowoc MII 302 Especificaciones Pagina 128

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 182
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 127
126 Part Number STH038 5/12
CONTROL BOARD RELAY TEST
The control board can be set to energize all relays for
3.5 minutes. This allows testing to verify control board
relays are closed and line voltage is available for ice
machine components - Water pump, dump valve,
water inlet valve, harvest valve(s), air compressor,
contactor/compressor/fan motor - The fan cycle
control must close to energize the fan motor.
1. Press power button to turn off ice machine.
2. Perform the following keystrokes on the display.
Press Menu, scroll down to Service and press the
right arrow
Scroll down to Diagnostics, press the right arrow
and select Diagnostics
Display reads Control Board, press right arrow
Scroll down to enbl relays and press right arrow to
start control board test
3. The control board will energize all relays and the
red light next to the relay. The red light indicates
the relay coil is energized.
Vista de pagina 127
1 2 ... 123 124 125 126 127 128 129 130 131 132 133 ... 181 182

Comentarios a estos manuales

Sin comentarios