Manitowoc MII 302 Especificaciones Pagina 147

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 182
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 146
Part Number STH038 5/12 145
WATER WILL NOT RUN INTO THE SUMP TROUGH
DURING THE FREEZE CYCLE
Step 1 Verify water is supplied to the ice machine.
Step 2 Scroll to Service/Diagnostics/Inputs and press
down arrow until Wtr Low and Wtr High are displayed.
A. Yes is displayed - Control board is receiving a
sensing water signal. Proceed to step 3.
B. No is displayed - Control board is not
receiving a sensing water signal. Proceed to
Control Board Diagnostics page 124.
Step 3 Disconnect water level probe, observe LCD
display text.
A. No is displayed - Clean the water level probe
and test interconnecting wiring.
B. Yes is displayed - Refer to Control Board
Diagnostics page 124
Vista de pagina 146
1 2 ... 142 143 144 145 146 147 148 149 150 151 152 ... 181 182

Comentarios a estos manuales

Sin comentarios