Part Number STH025 02/12 175
Freeze Cycle Operation
During the Freeze cycle, the water inlet valve
energizes and de-energizes in conjunction with the
water level probe located in the water trough.
During the first 45 seconds of the Freeze cycle:
The water inlet valve is ON when there is no water
in contact with the water level probes.
The water inlet valve turns OFF after water
contacts the water level probes for 3 continuous
seconds.
The water inlet valve will cycle ON and OFF once
in the prechill and up to two times in the freeze
cycle.
Maximum fill time is 6 minutes for single
evaporator.
After 45 seconds into the Freeze cycle:
The water inlet valve will cycle ON, and then OFF one
more time to refill the water trough. The water inlet
valve is now OFF for the duration of the freeze cycle.
Diagnostics
SYMPTOMS
Water trough overfills
Water trough will not fill
Display indicates a “Long Freeze” alert and may or
may not also indicate a safety limit 1
Ice production is low
WATER TROUGH OVERFILLING DURING THE
FREEZE CYCLE
Step 1 Press the power button and turn off the ice
machine.
Step 2 If water continues to flow with the ice machine
off, disconnect power. If water continues to flow verify
water pressure is below 80 psig before replacing the
water inlet valve.
Step 3 Check water level probe mounting and verify
secure wiring connections at the probe and control
board.
Step 4 Scroll to Service/Diagnostics/Inputs and press
down arrow until Wtr Low and Wtr High are displayed.