Part Number 000007661 6/12 45
RF1200C/RF2300C
Head Section with Rack Refrigeration system
When the toggle switch is placed in the ON position
the following controls must be in the closed position
before the ice machine will start:
A. Bin Thermostat
B. Ice Chute Safety Switch
C. Low Water Level Switch
Placing the toggle switch in the ON position starts the
gear motor. After the rotation speed sensor verifies
10 minutes of correct rotation the time delay ends and
the liquid line and suction solenoid valves energize.
The ice machine will continue to make ice until ice
contacts the bin thermostat and the liquid line and
suction solenoid valves close.
The ice machine remains off until ice no longer
contacts the bin thermostat.
NOTE: Refer to electrical flowchart for “RF1200C/
RFS1200C QuietQube Remote” on page 67 and
“RF2300C/RFS2300C QuietQube Remote” on
page 79 for Sequence of Operation detail.